The ET-4D2 is the ideal choice for tightly limited measurement tasks where the focus is on reliable warning of dangers while maintaining a favorable cost level.
Features
Number of transmitters:
- 1 to 4 (4-20mA)
Signal evaluation:
- Microcontroller with A/D converter
Alarm/fault/display:
- Illuminated graphic display (160 x 80) for showing measured values, messages and alarms
- 12 (3 x 4) red LEDs for alarm indication
- LEDs for displaying channel faults (4 x yellow), channel operation (4 x green), central operation (1 x green), central fault (1 x yellow)
User Interface:
- Menu-driven system via graphic display and button
- Fully configurable on the device without any tools
- 3 password-protected operating levels
Alarm evaluation:
- 3 freely adjustable alarm thresholds per channel
- Monitoring: exceeding, falling below or min./max.
- Configurable latching of each alarm
Relay, potential-free:
- 12 changeover contacts 230 V / 5 A (total switching current: max. 10 A), freely configurable with alarms 1 to 3 and transmitter fault
- 2 changeover contacts 230 V / 5 A for maintenance mode and device malfunction
Additional functions:
- Zero point and sensitivity adjustment of the measuring channels
- RS 232/RS 485 interface for communication with external peripherals (PC or PLT system)
- Key switch function (maintenance mode)
- Horn reset
- New value alert
- 4 digital inputs, floating
- 4 analog outputs 4-20 mA/0-10 V, floating (only ET-4DA2)
Operating temperature:
- -10 °C to +40 °C, humidity: non-condensing
Storage Temperature:
- -25 °C to +60 °C, humidity: non-condensing